Loading... Loading...
English
French

DENCO Technologies

DENCO TECHNOLOGIES - 104, rue Bellocier - 89107 SENS CEDEX - France

Especially conceived to answer to some office automation applications requirements in particular head offices and administrative premises

The economical

DESCRIPTION

Composition
Nominal standard size 600 x 600 mm
A high density particled board of standard thickness 38 or 30 mm (1)
A deep folded closed corner folded corrosion protected steel tray (2)

PERFORMANCES

Fire rating
The COMPACT panel is rated M1 (in plenum) (PV n° 12211.05)

Electrostatic properties
Depending on the quality of covering and the composition, vary from 5 x 108
to 2 x 1012 ohms (according to standard NFP 62001)

Sound attenuation Dn (rose)
Depending on the thickness of the panel, the understructure and the covering, varie from 45 to 50 dbA

OPTIONS

For greater load bearing capacity :
top corrosion protected steel skin 0,5 mm thick (COMPACT 30 or 38.5/5)

For improved resistance to ambient humidity and handling facility :
- top aluminum skin 0,2 mm thick
- top face varnished

COVERINGS

The COMPACT panel can be supplied :
- bare (SR) for loose lay carpet to be laid on site.
- with a factory bonded covering as massive parquet, textile or reconstituted stone.

COMPACT 30.5 and 38.5
Point loads
 
COMPACT 30.5
COMPACT 38.5
 
Understructure
Understructure
Covering
Stringerless
Lockable
Stringerless
Lockable
Without
 
2A
(2B or 4C)
2A
(4B or 5C)
2A
(2B or 4C)
3A
(5B or 5C)
Load classes according to norm NF EN 12825
Safety factor = 2

The polyvalent steel/alu

DM 30.5 or DM 38.5
Point loads
 
DM 30.5
DM 38.5
 
Understructure
Understructure
Covering
Stringerless
Lockable
Stringerless
Lockable
Without
 
1A
(1B or 2C)
2A
(4B or 5C)
2A
(3B or 4C)
3A
(5B or 5C)
Laminate
 
1A
(2B or 3C)
2A
(4B or 5C)
2A
(4B or 4C)
5A
(5B or 5C)
Load classes according to norm NF EN 12825
Safety factor = 2
DALU 38.2
Point loads
 
DALU 38.2
 
Understructure
Covering
Stringerless
Lockable
Without
1A (1B or 2C)
2A (4B or 5C)
Laminate
1A (2B or 3C)
2A (2B or 5C)
Load classes according to norm NF EN 12825
Safety factor = 2

DESCRIPTION

Composition
Nominal standard 600 x 600 mm.
High density particle board of standard thickness 38 or 30 mm. (1)

Peripheral PVC edging hot-melt pressure bonded (3)

a bottom protected steel skin 0,5 mm thick for the DM panel. (2)

top aluminium skin 0,2 mm for the DALU panel. (2)

PERFORMANCES

Fire rating
The DM and DALU panels are rated M1 (in plenum) (PV N° 12211.05)

Electrostatic properties
Depending of the quality and nature of the covering, vary from 5 x 105
to 2 x 1012 ohms (according to norm NFP 62001)

Sound attenuation Dn (rose)
- DM panel : varies from 38 to 45 dbA depending on the understructure and the covering.
- DALUpanel : varies from 43 to 44 dbA depending on the understructure and the covering.

COVERINGS

The DM and DALU panels can be supplied bare (SR) for loose laid carpet to be laid on site or with the following factory bonded coverings (4) : laminate, vinyl, linoleum, rubber, textile, granit, reconstituted stone or massive parquet.

OPTIONS

For greater load bearing capacity :
- Top corrosion protected steel skin 0,5 mm
 
 
 
 
 
 

NB : A system classed 1A is a system which the ultimate load is at least 4 kN (load classe 1). The working load is at least 2 kN, with a safety factor of 2, for a deflection less than 2,5 mm (deflection class A).
See tables below for the other classes
 
Class
Class
Class
Class
Class
Class
Deflection class
Maximum deflection
Load class
1
2
3
4
5
6
A (the more stringent)
2,5 mm
Class break
> 4 kN
> 6 kN
> 8 kN
> 9 kN
> 10 kN
> 12 kN
B
3 mm
Working class
> 2 kN
> 3 kN
> 4 kN
> 4,5 kN
> 5 kN
> 6 kN
C (the less stringent)
4 mm
top aluminium skin 0,2 mm thick
-
Welded steel frame
-
COMPACT 25.5.5/M0
-

AUTO SUPPORTINT SYSTEM

-

Stability

-

raised access floors conception

-
Sealing
-

Covering linoleum

-

Covering linoleum

-
Stringers
-

incombustible

-
fire security
-
computing bays
-

Access ramp

-
DALU panel
-

SEC 800 perforated

-
Easy to carrier
-

COMPACT 30.5/M0

-

Reinforcement

-
Railing of ventilation
-

Special for heavy loads

-

static electricity dissipating gasket

-

Suction lifters

-
Steps
-

Special understructure meshing

-
Covering granit
-
Splints of connecting
-

Top corrosion protected steel skin 0,5 mm

-
COMPACT 30/M0 and 25/M0 panels
-

Wooden strips

-
Covering laminate
-

Clamp for panel with carpet or fitted carpet

-
cable tray
-

David

-
crossing of cable tray
-

NF EN 12825

-
MODULPACT
-
DALU 38.2
-
massive parquet
-

Partition

-

Pedestals for low floors