Loading...
The panels are directly put down on heads of jacks provided with a gasket conductive shock absorber.
Pedestals are generally stuck on the basic ground with a specific adhesive.
They allow a regulation level of the raised floor.
The fixation of a possible earth wire can be realized by springing or crimping (according to request).

The panels are put down on stringers
Stringers can be added to improve :
- the horizontal stability of the floor ,
- the waterproofness of the plenum ,
- and\or the resistance to the load.
Applicable in particular for heights of floors superior to 500 mm or zones subjected to frequent passages of rolling loads.
VBa - Pedestal for floors of finished floor height from 50 to 120 mm
Composition
Corrosion protected steel base
, M 16 corrosion protected threaded steel stud
welded on the base, M 16 tapped steel head
, notched, static electricity dissipating gasket with panels retaining lugs
.
Height adjustment ± 15 mm
Point loads
450 daN
DAVID - Pedestal for floors of finished floor height from 120 to 800 mm (*)
(*) approx. According diameter of threaded stud
Composition
Corrosion protected steel base
, - 80 x 80 or 100 x 100 mm, M 16, M18 or M 20 corrosing protected threaded steel stud
welded on the base.
Corrosion protected steel
, castellated levelling nut, plain bore aluminium head
, static electricity dissipating gasket
, spring clips for fixing the earth wire.
Height adjustment ± 25 mm from the nominal height
Point loads
500 daN - floor height < 300 mm
450 daN : floor height < 800 mm
VGH - Pedestal for floors of finished floor height from 800 to 1200 mm
Composition
Corrosion protected steel base 100 x 100 mm
, corrosion protected steel square tube 22 x 22
fitted on the base
Locking nut
of the stud in the tube, M 18 corrosion protected threaded steel stud 
Castellated levelling nut
supporting the head.
Plain bore aluminium head 
Height adjustment ± 25 mm
point loads
520 daN
Composition
U-shaped steel corrosion protected profiles. The height and the thickness can be different according to the required performances (plenum sealing, stability), dissipating gasket on the head of the pedestal
OPTION : static electricity dissipating gasket on the stringer.